CPU-SB10/64(FIT)
SUCHEN SIE DIE PASSENDE
INDUSTRIELLE LÖSUNG?
Entdecken Sie Embedded-, Kommunikations- und Automatisierungslösungen für Ihre Anwendung.
DIO-16/16(FIT)
Ethernet isolated 16/16 DIO Module
280,00 EUR
inkl. Umsatzsteuer 333,20 EUR
- Dual 16-channel I/O configuration: Provides 16 opto-isolated digital inputs (12–24 V DC) and 16 opto-isolated digital outputs (12–48 V DC).
- Optical isolation: Each channel is electrically isolated via optocouplers, ensuring high noise immunity and protection against ground loops.
- Flexible power domains: Separate external power supplies can be used for each common pin group, allowing mixed-voltage operation.
- High-current open collector outputs: Capable of sinking up to 150 mA per channel at 24 V DC or 50 mA at 48 V DC.
- Digital filtering: Built-in hardware digital filter (programmable 0.25 µs–131 ms) suppresses noise and contact chattering on input lines.
- Interrupt capability: All input channels can be configured as interrupt sources with selectable rising or falling edge triggers.
- Stackable modular design: Connects laterally to controller modules (CPU-CAxx(FIT)GY or CPU-SBxx(FIT)GY) without a backplane, simplifying system expansion.
- DIN-rail mounting: Standard 35 mm DIN rail clip for quick installation.
- Device ID rotary switch: Hardware rotary selector (0–7) for easy module addressing.
- Web and API control: Supports direct I/O access, memory-mapped control, Windows drivers, and web-based configuration via SVR-MMF2(FIT).
- Industrial-grade reliability: Designed for 0–50 °C operation, 10–90 % RH humidity, and compliance with IEC/EN industrial EMC standards.
- Optical isolation: Each channel is electrically isolated via optocouplers, ensuring high noise immunity and protection against ground loops.
- Flexible power domains: Separate external power supplies can be used for each common pin group, allowing mixed-voltage operation.
- High-current open collector outputs: Capable of sinking up to 150 mA per channel at 24 V DC or 50 mA at 48 V DC.
- Digital filtering: Built-in hardware digital filter (programmable 0.25 µs–131 ms) suppresses noise and contact chattering on input lines.
- Interrupt capability: All input channels can be configured as interrupt sources with selectable rising or falling edge triggers.
- Stackable modular design: Connects laterally to controller modules (CPU-CAxx(FIT)GY or CPU-SBxx(FIT)GY) without a backplane, simplifying system expansion.
- DIN-rail mounting: Standard 35 mm DIN rail clip for quick installation.
- Device ID rotary switch: Hardware rotary selector (0–7) for easy module addressing.
- Web and API control: Supports direct I/O access, memory-mapped control, Windows drivers, and web-based configuration via SVR-MMF2(FIT).
- Industrial-grade reliability: Designed for 0–50 °C operation, 10–90 % RH humidity, and compliance with IEC/EN industrial EMC standards.
Comprehensive Product Summary – CONTEC DIO-16/16(FIT)GY Ethernet Isolated Digital I/O Module
### 1. Product Overview
Product Name: Ethernet Isolated 16/16 Digital I/O Module
Model: DIO-16/16(FIT)GY
Series: F&eIT Series
Article Number: DIO-16/16(FIT)
Manufacturer: CONTEC CO., LTD. (Japan)
Product Category: Ethernet-based isolated digital input/output expansion module for industrial automation and control systems.
Related Models:
- DI-32(FIT)GY – 32-channel isolated digital input module
- DO-32(FIT)GY – 32-channel isolated digital output module
The DIO-16/16(FIT)GY is a compact, DIN-rail mountable Ethernet I/O module designed to provide 16 opto-isolated digital inputs and 16 opto-isolated digital outputs. It is part of CONTEC’s modular F&eIT system, which allows flexible configuration of distributed I/O and control networks.
### 2. Key Features
- Dual 16-channel I/O configuration: Provides 16 opto-isolated digital inputs (12–24 V DC) and 16 opto-isolated digital outputs (12–48 V DC).
- Optical isolation: Each channel is electrically isolated via optocouplers, ensuring high noise immunity and protection against ground loops.
- Flexible power domains: Separate external power supplies can be used for each common pin group, allowing mixed-voltage operation.
- High-current open collector outputs: Capable of sinking up to 150 mA per channel at 24 V DC or 50 mA at 48 V DC.
- Digital filtering: Built-in hardware digital filter (programmable 0.25 µs–131 ms) suppresses noise and contact chattering on input lines.
- Interrupt capability: All input channels can be configured as interrupt sources with selectable rising or falling edge triggers.
- Stackable modular design: Connects laterally to controller modules (CPU-CAxx(FIT)GY or CPU-SBxx(FIT)GY) without a backplane, simplifying system expansion.
- DIN-rail mounting: Standard 35 mm DIN rail clip for quick installation.
- Device ID rotary switch: Hardware rotary selector (0–7) for easy module addressing.
- Web and API control: Supports direct I/O access, memory-mapped control, Windows drivers, and web-based configuration via SVR-MMF2(FIT).
- Industrial-grade reliability: Designed for 0–50 °C operation, 10–90 % RH humidity, and compliance with IEC/EN industrial EMC standards.
### 3. Technical Specifications
Electrical Characteristics
| Parameter | Specification |
|------------|---------------|
| Input Type | Opto-isolated, compatible with current sink/source outputs |
| Input Voltage Range | 12–24 V DC (±15 %) |
| Input Resistance | 3 kΩ |
| Input ON Current | ≥ 3.4 mA |
| Input OFF Current | ≤ 0.16 mA |
| Input Points | 16 points (16 points/common) |
| Input Response Time | ≤ 1 ms |
| Output Type | Opto-isolated open collector (current sink) |
| Output Voltage Range | 12–48 V DC (±15 %) |
| Output Current | 150 mA @ 12–24 V DC / 50 mA @ 36–48 V DC (per channel) |
| Output Points | 16 points (16 points/common) |
| Output Response Time | ≤ 1 ms |
| Internal Power Consumption | 5 V DC (±5 %) 150 mA max |
| External Circuit Power Supply | 12–48 V DC (±15 %) |
| Signal Extension Distance | Approx. 50 m (depending on wiring environment) |
Mechanical and Physical
| Parameter | Specification |
|------------|---------------|
| Dimensions (W × D × H) | 25.2 × 64.7 × 94.0 mm (excluding protrusions) |
| Weight | Approx. 100 g |
| Mounting | 35 mm DIN rail (one-touch mechanism) |
| Connection Method | Stack connection via integrated side connector |
| Connector Type | 3.5 mm pitch, 36-pin Phoenix Contact MCDN1.5/18-G1-3.5P26THR |
| Included Plug | FMC1.5/18-ST-3.5 (Phoenix Contact) |
| Applicable Wire Gauge | AWG 24–16 |
Environmental Conditions
| Parameter | Specification |
|------------|---------------|
| Operating Temperature | 0 – 50 °C |
| Storage Temperature | –10 – 60 °C |
| Operating Humidity | 10 – 90 % RH (non-condensing) |
| Corrosive Gases | None |
| Dust | Not excessive |
| Vibration Resistance | 10–57 Hz / 0.15 mm, 57–150 Hz / 2 G (IEC 68‑2‑6) |
| Shock Resistance | 15 G, 11 ms half‑sine (IEC 68‑2‑27) |
| Noise Immunity | AC line 2 kV, signal line 1 kV (IEC 1000‑4‑4 Level 3) |
| ESD Immunity | Contact 4 kV, air 8 kV (IEC 1000‑4‑2 Level 2/3) |
### 4. Functionality
Operating Principle:
The DIO-16/16(FIT)GY acts as a digital I/O expansion module for CONTEC’s F&eIT controllers. It receives and transmits digital signals between external field devices (sensors, switches, relays) and the controller CPU. Inputs are optically isolated and read by the controller through I/O or memory-mapped access. Outputs are driven by open-collector transistors, allowing control of external loads such as relays, lamps, or solenoids.
Use Cases and Applications:
- Factory automation and process control
- Machine I/O expansion for PLC or embedded controllers
- Remote monitoring and data acquisition over Ethernet
- Industrial equipment interlocking and alarm systems
- Distributed I/O in building automation or test systems
Compatibility:
- Controller Modules: CPU-CAxx(FIT)GY (Ethernet I/O controller), CPU-SBxx(FIT)GY (microcontroller unit)
- Server Unit: SVR-MMF2(FIT) for web-based monitoring
- Software Interfaces: API‑CAP(W32), API‑SBP(W32), FIT Protocol, and web browser configuration
Control Methods:
- I/O Address Map Access: Direct port-level control when connected to CPU‑SBxx(FIT)GY
- Memory Address Map Access: Network-based memory-mapped control via CPU‑CAxx(FIT)GY
- Windows Driver Control: Through CONTEC’s API libraries and FIT protocol
- Web Control: Browser-based configuration and monitoring via SVR‑MMF2(FIT)
### 5. Components & Accessories
Package Contents:
1. DIO‑16/16(FIT)GY module (1 pc)
2. Interface connector plug (Phoenix Contact FMC1.5/18‑ST‑3.5)
3. First Step Guide (printed manual)
4. CD‑ROM [F&eIT Series Setup Disk] containing drivers, manuals, and utilities
Optional Accessories:
- Additional connector plugs for external wiring
- DIN rail mounting hardware (standard included)
- Compatible controller modules (CPU‑CAxx(FIT)GY, CPU‑SBxx(FIT)GY)
- Power supply unit POW‑AD22GY (recommended for noise immunity compliance)
Connectors:
- Two 18‑pin connectors (X and Y) for input and output groups
- Rated current: 6.0 A
- Wire insertion: push‑button type, 9–10 mm strip length
### 6. Installation & Setup
Mounting:
- Snap‑fit onto a 35 mm DIN rail.
- Stack laterally with controller modules using the integrated side connector.
- Ensure adequate ventilation and avoid excessive vibration or heat sources.
Device ID Configuration:
- Rotary switch on the front panel (range 0–7).
- Factory default: Device ID = 0.
- Up to 8 modules can be addressed per controller.
Wiring:
- Use AWG 24–16 wires.
- Strip 9–10 mm insulation and insert into the push terminal while pressing the orange release button.
- Separate commons (C0, C1, C2) allow independent power domains for input and output groups.
Connection Examples:
- Input: Connect external 12–24 V DC source through sensors or switches to input pins (IN00–IN17).
- Output: Connect loads (relays, lamps) between output pins (OUT00–OUT17) and external 12–48 V DC supply.
- Surge Protection: Use diodes or zener diodes across inductive loads; place within 50 cm of the load.
Precautions:
- Power off the controller before connecting or disconnecting modules.
- Do not modify or open the module casing.
- Avoid static discharge and magnetic interference during installation.
### 7. Performance & Capabilities
Speed and Response:
- Input and output response times ≤ 1 ms.
- Digital filter configurable from 0.25 µs to 131 ms for noise suppression.
- Interrupt latency dependent on controller configuration (IRQ 5, 7, 9 supported).
Capacity:
- 16 input + 16 output channels per module.
- Stackable up to 8 modules (128 I/O points total).
- Signal extension up to 50 m depending on wiring quality.
Efficiency and Reliability:
- Opto‑isolation ensures high noise immunity.
- Open‑collector outputs allow flexible load control.
- Digital filter and interrupt functions enhance real‑time responsiveness.
Limitations:
- Outputs default to OFF at power‑on.
- Total current draw must not exceed controller power supply capacity (3.0 A max through stack connector).
- Digital filter applies globally to all input channels (not per‑channel configurable).
### 8. Standards & Compliance
Regulatory Compliance:
- FCC Part 15 Class A (for commercial/industrial environments)
- EN61000‑4‑2/‑4 (ESD and EFT immunity)
- IEC68‑2‑6/‑27 (vibration and shock resistance)
- RoHS compliant (lead‑free manufacturing)
Safety and Environmental:
- Designed for industrial control panels and automation systems.
- No corrosive gas or excessive dust environments.
- Meets CONTEC’s internal quality and reliability standards.
EMC and Noise Immunity:
- Line noise: AC line 2 kV, signal line 1 kV (IEC1000‑4‑4 Level 3)
- Static discharge: Contact 4 kV, air 8 kV (IEC1000‑4‑2 Level 2/3)
### 9. Additional Information
Warranty:
- Limited One‑Year Warranty from date of purchase.
- Covers defects in materials and workmanship.
- Excludes damage from misuse, modification, or improper handling.
- RMA (Return Merchandise Authorization) required for service.
Support & Resources:
- Websites:
- Japanese: [https://www.contec.co.jp](https://www.contec.co.jp)
- English: [https://www.contec.com](https://www.contec.com)
- Chinese: [https://www.contec.com.cn](https://www.contec.com.cn)
- Manuals, drivers, and sample programs available for free download.
- Technical support via authorized distributors and CONTEC offices.
Maintenance:
- Periodically inspect ventilation slits for dust or obstruction.
- Store in original packaging when not in use.
- Dispose of according to local electronic waste regulations.
Firmware & Software Updates:
- Updated drivers and FIT protocol libraries available on CONTEC’s website.
- Compatible with Windows API‑CAP(W32) and API‑SBP(W32) development kits.
- Supports FIT Protocol for network‑based I/O control.
### Summary
The CONTEC DIO‑16/16(FIT)GY is a robust, Ethernet‑enabled digital I/O module engineered for industrial automation environments requiring reliable, isolated signal interfacing. With 16 inputs and 16 outputs, opto‑isolation, programmable digital filtering, and interrupt capabilities, it provides a flexible and noise‑resistant interface between field devices and control systems. Its modular F&eIT architecture allows seamless stacking with controller units, while DIN‑rail mounting and plug‑in connectors simplify installation. Compliance with international EMC and safety standards ensures dependable operation in demanding industrial conditions.
This module is ideal for engineers integrating distributed I/O in factory automation, process control, or remote monitoring systems where compactness, reliability, and configurability are critical.
### 1. Product Overview
Product Name: Ethernet Isolated 16/16 Digital I/O Module
Model: DIO-16/16(FIT)GY
Series: F&eIT Series
Article Number: DIO-16/16(FIT)
Manufacturer: CONTEC CO., LTD. (Japan)
Product Category: Ethernet-based isolated digital input/output expansion module for industrial automation and control systems.
Related Models:
- DI-32(FIT)GY – 32-channel isolated digital input module
- DO-32(FIT)GY – 32-channel isolated digital output module
The DIO-16/16(FIT)GY is a compact, DIN-rail mountable Ethernet I/O module designed to provide 16 opto-isolated digital inputs and 16 opto-isolated digital outputs. It is part of CONTEC’s modular F&eIT system, which allows flexible configuration of distributed I/O and control networks.
### 2. Key Features
- Dual 16-channel I/O configuration: Provides 16 opto-isolated digital inputs (12–24 V DC) and 16 opto-isolated digital outputs (12–48 V DC).
- Optical isolation: Each channel is electrically isolated via optocouplers, ensuring high noise immunity and protection against ground loops.
- Flexible power domains: Separate external power supplies can be used for each common pin group, allowing mixed-voltage operation.
- High-current open collector outputs: Capable of sinking up to 150 mA per channel at 24 V DC or 50 mA at 48 V DC.
- Digital filtering: Built-in hardware digital filter (programmable 0.25 µs–131 ms) suppresses noise and contact chattering on input lines.
- Interrupt capability: All input channels can be configured as interrupt sources with selectable rising or falling edge triggers.
- Stackable modular design: Connects laterally to controller modules (CPU-CAxx(FIT)GY or CPU-SBxx(FIT)GY) without a backplane, simplifying system expansion.
- DIN-rail mounting: Standard 35 mm DIN rail clip for quick installation.
- Device ID rotary switch: Hardware rotary selector (0–7) for easy module addressing.
- Web and API control: Supports direct I/O access, memory-mapped control, Windows drivers, and web-based configuration via SVR-MMF2(FIT).
- Industrial-grade reliability: Designed for 0–50 °C operation, 10–90 % RH humidity, and compliance with IEC/EN industrial EMC standards.
### 3. Technical Specifications
Electrical Characteristics
| Parameter | Specification |
|------------|---------------|
| Input Type | Opto-isolated, compatible with current sink/source outputs |
| Input Voltage Range | 12–24 V DC (±15 %) |
| Input Resistance | 3 kΩ |
| Input ON Current | ≥ 3.4 mA |
| Input OFF Current | ≤ 0.16 mA |
| Input Points | 16 points (16 points/common) |
| Input Response Time | ≤ 1 ms |
| Output Type | Opto-isolated open collector (current sink) |
| Output Voltage Range | 12–48 V DC (±15 %) |
| Output Current | 150 mA @ 12–24 V DC / 50 mA @ 36–48 V DC (per channel) |
| Output Points | 16 points (16 points/common) |
| Output Response Time | ≤ 1 ms |
| Internal Power Consumption | 5 V DC (±5 %) 150 mA max |
| External Circuit Power Supply | 12–48 V DC (±15 %) |
| Signal Extension Distance | Approx. 50 m (depending on wiring environment) |
Mechanical and Physical
| Parameter | Specification |
|------------|---------------|
| Dimensions (W × D × H) | 25.2 × 64.7 × 94.0 mm (excluding protrusions) |
| Weight | Approx. 100 g |
| Mounting | 35 mm DIN rail (one-touch mechanism) |
| Connection Method | Stack connection via integrated side connector |
| Connector Type | 3.5 mm pitch, 36-pin Phoenix Contact MCDN1.5/18-G1-3.5P26THR |
| Included Plug | FMC1.5/18-ST-3.5 (Phoenix Contact) |
| Applicable Wire Gauge | AWG 24–16 |
Environmental Conditions
| Parameter | Specification |
|------------|---------------|
| Operating Temperature | 0 – 50 °C |
| Storage Temperature | –10 – 60 °C |
| Operating Humidity | 10 – 90 % RH (non-condensing) |
| Corrosive Gases | None |
| Dust | Not excessive |
| Vibration Resistance | 10–57 Hz / 0.15 mm, 57–150 Hz / 2 G (IEC 68‑2‑6) |
| Shock Resistance | 15 G, 11 ms half‑sine (IEC 68‑2‑27) |
| Noise Immunity | AC line 2 kV, signal line 1 kV (IEC 1000‑4‑4 Level 3) |
| ESD Immunity | Contact 4 kV, air 8 kV (IEC 1000‑4‑2 Level 2/3) |
### 4. Functionality
Operating Principle:
The DIO-16/16(FIT)GY acts as a digital I/O expansion module for CONTEC’s F&eIT controllers. It receives and transmits digital signals between external field devices (sensors, switches, relays) and the controller CPU. Inputs are optically isolated and read by the controller through I/O or memory-mapped access. Outputs are driven by open-collector transistors, allowing control of external loads such as relays, lamps, or solenoids.
Use Cases and Applications:
- Factory automation and process control
- Machine I/O expansion for PLC or embedded controllers
- Remote monitoring and data acquisition over Ethernet
- Industrial equipment interlocking and alarm systems
- Distributed I/O in building automation or test systems
Compatibility:
- Controller Modules: CPU-CAxx(FIT)GY (Ethernet I/O controller), CPU-SBxx(FIT)GY (microcontroller unit)
- Server Unit: SVR-MMF2(FIT) for web-based monitoring
- Software Interfaces: API‑CAP(W32), API‑SBP(W32), FIT Protocol, and web browser configuration
Control Methods:
- I/O Address Map Access: Direct port-level control when connected to CPU‑SBxx(FIT)GY
- Memory Address Map Access: Network-based memory-mapped control via CPU‑CAxx(FIT)GY
- Windows Driver Control: Through CONTEC’s API libraries and FIT protocol
- Web Control: Browser-based configuration and monitoring via SVR‑MMF2(FIT)
### 5. Components & Accessories
Package Contents:
1. DIO‑16/16(FIT)GY module (1 pc)
2. Interface connector plug (Phoenix Contact FMC1.5/18‑ST‑3.5)
3. First Step Guide (printed manual)
4. CD‑ROM [F&eIT Series Setup Disk] containing drivers, manuals, and utilities
Optional Accessories:
- Additional connector plugs for external wiring
- DIN rail mounting hardware (standard included)
- Compatible controller modules (CPU‑CAxx(FIT)GY, CPU‑SBxx(FIT)GY)
- Power supply unit POW‑AD22GY (recommended for noise immunity compliance)
Connectors:
- Two 18‑pin connectors (X and Y) for input and output groups
- Rated current: 6.0 A
- Wire insertion: push‑button type, 9–10 mm strip length
### 6. Installation & Setup
Mounting:
- Snap‑fit onto a 35 mm DIN rail.
- Stack laterally with controller modules using the integrated side connector.
- Ensure adequate ventilation and avoid excessive vibration or heat sources.
Device ID Configuration:
- Rotary switch on the front panel (range 0–7).
- Factory default: Device ID = 0.
- Up to 8 modules can be addressed per controller.
Wiring:
- Use AWG 24–16 wires.
- Strip 9–10 mm insulation and insert into the push terminal while pressing the orange release button.
- Separate commons (C0, C1, C2) allow independent power domains for input and output groups.
Connection Examples:
- Input: Connect external 12–24 V DC source through sensors or switches to input pins (IN00–IN17).
- Output: Connect loads (relays, lamps) between output pins (OUT00–OUT17) and external 12–48 V DC supply.
- Surge Protection: Use diodes or zener diodes across inductive loads; place within 50 cm of the load.
Precautions:
- Power off the controller before connecting or disconnecting modules.
- Do not modify or open the module casing.
- Avoid static discharge and magnetic interference during installation.
### 7. Performance & Capabilities
Speed and Response:
- Input and output response times ≤ 1 ms.
- Digital filter configurable from 0.25 µs to 131 ms for noise suppression.
- Interrupt latency dependent on controller configuration (IRQ 5, 7, 9 supported).
Capacity:
- 16 input + 16 output channels per module.
- Stackable up to 8 modules (128 I/O points total).
- Signal extension up to 50 m depending on wiring quality.
Efficiency and Reliability:
- Opto‑isolation ensures high noise immunity.
- Open‑collector outputs allow flexible load control.
- Digital filter and interrupt functions enhance real‑time responsiveness.
Limitations:
- Outputs default to OFF at power‑on.
- Total current draw must not exceed controller power supply capacity (3.0 A max through stack connector).
- Digital filter applies globally to all input channels (not per‑channel configurable).
### 8. Standards & Compliance
Regulatory Compliance:
- FCC Part 15 Class A (for commercial/industrial environments)
- EN61000‑4‑2/‑4 (ESD and EFT immunity)
- IEC68‑2‑6/‑27 (vibration and shock resistance)
- RoHS compliant (lead‑free manufacturing)
Safety and Environmental:
- Designed for industrial control panels and automation systems.
- No corrosive gas or excessive dust environments.
- Meets CONTEC’s internal quality and reliability standards.
EMC and Noise Immunity:
- Line noise: AC line 2 kV, signal line 1 kV (IEC1000‑4‑4 Level 3)
- Static discharge: Contact 4 kV, air 8 kV (IEC1000‑4‑2 Level 2/3)
### 9. Additional Information
Warranty:
- Limited One‑Year Warranty from date of purchase.
- Covers defects in materials and workmanship.
- Excludes damage from misuse, modification, or improper handling.
- RMA (Return Merchandise Authorization) required for service.
Support & Resources:
- Websites:
- Japanese: [https://www.contec.co.jp](https://www.contec.co.jp)
- English: [https://www.contec.com](https://www.contec.com)
- Chinese: [https://www.contec.com.cn](https://www.contec.com.cn)
- Manuals, drivers, and sample programs available for free download.
- Technical support via authorized distributors and CONTEC offices.
Maintenance:
- Periodically inspect ventilation slits for dust or obstruction.
- Store in original packaging when not in use.
- Dispose of according to local electronic waste regulations.
Firmware & Software Updates:
- Updated drivers and FIT protocol libraries available on CONTEC’s website.
- Compatible with Windows API‑CAP(W32) and API‑SBP(W32) development kits.
- Supports FIT Protocol for network‑based I/O control.
### Summary
The CONTEC DIO‑16/16(FIT)GY is a robust, Ethernet‑enabled digital I/O module engineered for industrial automation environments requiring reliable, isolated signal interfacing. With 16 inputs and 16 outputs, opto‑isolation, programmable digital filtering, and interrupt capabilities, it provides a flexible and noise‑resistant interface between field devices and control systems. Its modular F&eIT architecture allows seamless stacking with controller units, while DIN‑rail mounting and plug‑in connectors simplify installation. Compliance with international EMC and safety standards ensures dependable operation in demanding industrial conditions.
This module is ideal for engineers integrating distributed I/O in factory automation, process control, or remote monitoring systems where compactness, reliability, and configurability are critical.
- CPU-SB10/64(FIT) - Ethernet CPU Module
- CPU-CA10(FIT) - Ethernet IO controller